BC - 102 NORTHSIDE SUMPUMP
BC - 102 NORTHSIDE SUMPUMP
KW - 0.3
SFU - 63 A
FUSE - 50A 3 nos
O/L - 12.5 to 20A
LEVEL CONTROLLER -
NO NO C - LOW LEVEL
NO NO C - I
NO NO C - HIGH LEVEL
NO NO C -
L - 110V +ve Side - Supply from 2A Control Supply MCB
N - 110 -ve Side
LEVEL PROAF -
E - (G) - (T1) -
Pr 1 - (L) - (T2) - Low Level
Pr 2 - ( H) - (T3) - High Level
H1 - High Level ( 4 number of Feruling wire come out from Water Level Controller No point and connect there.
DLL - 2 number Feruling Low Level NO point of Water Level Controller and connect it's+Ve point.
1 Number Feruling wire +Ve point side come out from 2A Control Supply MCB and connect at Low Level C point of Water Level Controller.
H4 - Pump OFF
MCB - 2A (Control Supply)
T1 - ON Delay Timer ( 0 to 30 Min) Again 3number +ve 110V supply Feruling wire come out from Water Level Controller High Level NO point and connect there.
OVERLOAD RELAY - 1
110V +Ve supply come out from 2A MCB and connect NO point of Overload - 1 (97) and 5 number Feruling wire come out from Overload - 1 ( 98) and connect
H3 - Pump Overload Indication Lamp.
CONTROL TRANSFORMER -
Xmer 415/230V AC 250 VA
and out put Supply is 110/110
DRAWING
- Why INCOMER on which is according the Cercuit the pump module Dll Auxiliary Contacter and T1 on delay Timer Chartering ? (Date of problem - 29th April 2024)
- Voltage unbalance, in my opinion, is the main cause of chartering.
- The input and output voltages for the control transfer should be checked first.The stepdown output voltage is not constant at 250 volts AC, whereas the measured value of the input voltage of the Control Transfer is 415 volts AC.
- Once more, after removing the wire used for the circuit at the Control Transfer output side.There is a 250V AC value.
- Ultimately, the water level controller's sensor point is malfunctioning, according to the circuit, which results in an output NO NC point that is not functioning correctly and an inaccurate output voltage.
- Once more, if you sort the data independently at water Level Controller, the sumpup will start up without a hitch. No point to Commn point of DLL Auxiliary Contacter and T1 on delay Timer.