BC - 102 NORTHSIDE SUMPUMP

 BC - 102 NORTHSIDE SUMPUMP



45 watts ppp amplifier PUMP - 1
KW - 0.3 
SFU - 63 A
FUSE - 50A 3 nos 
O/L - 12.5 to 20A









45 watts ppp amplifier

LEVEL CONTROLLER -

NO NO C - LOW LEVEL 

NO NO C - I

NO NO C - HIGH LEVEL 

NO NO C - 


L - 110V +ve Side - Supply from 2A Control Supply MCB

N - 110 -ve Side


LEVEL PROAF -

E - (G) - (T1) -

Pr 1 - (L) - (T2) - Low Level 

Pr 2 - ( H) - (T3) - High Level 


H1 - High Level  ( 4 number of Feruling wire come out from Water Level Controller No point and connect there.

DLL -  2 number Feruling Low Level NO point of Water Level Controller and connect it's+Ve point.

1 Number Feruling wire +Ve point side come out from 2A Control Supply MCB and connect at Low Level C point of Water Level Controller.


H2 - Pump ON

H4 - Pump OFF


MCB - 2A  (Control Supply)

T1 - ON Delay Timer ( 0 to 30 Min) Again 3number +ve 110V supply Feruling wire come out from Water Level Controller High Level NO point and connect there.


45 watts ppp amplifier OVERLOAD RELAY - 1

110V +Ve supply come out from 2A MCB and connect NO point of Overload - 1   (97) and 5 number Feruling wire come out from Overload - 1 ( 98) and connect 

H3  - Pump Overload  Indication Lamp.


45 watts ppp amplifier

CONTROL TRANSFORMER -

Xmer 415/230V AC 250 VA

and out put Supply is 110/110






45 watts ppp amplifierCP 1 - START CONTACTOR for Pump 1










CONTROL CIRCUIT WIRE DETAILS -

STOP P.B. - ( The control supply comeout from 6A MCB and connect at Em.Stop NC point one Again other side NC point of Stop P.B. wire come out and connect at Auto/Manual Switch)

Common Point of Selector switch - 7
Auto Mode - 7
Manual Mode - 13
Pump Motor 1 - 8
Pump Motor 2 - 9



DRAWING 







PROBLEM AND RECTIFY   -:

  1. Why INCOMER on which is according the Cercuit the pump module Dll Auxiliary Contacter and T1 on delay Timer Chartering ? (Date of problem - 29th April 2024)
  • Voltage unbalance, in my opinion, is the main cause of chartering.
  • The input and output voltages for the control transfer should be checked first.The stepdown output voltage is not constant at 250 volts AC, whereas the measured value of the input voltage of the Control Transfer is 415 volts AC.
  • Once more, after removing the wire used for the circuit at the Control Transfer output side.There is a 250V AC value.
  • Ultimately, the water level controller's sensor point is malfunctioning, according to the circuit, which results in an output NO NC point that is not functioning correctly and an inaccurate output voltage.
  • Once more, if you sort the data independently at water Level Controller, the sumpup will start up without a hitch. No point to Commn point of DLL Auxiliary Contacter and T1 on delay Timer.